All fixtures with the potential to carry grease-bearing wastewater or solids shall be plumbed to the grease trap/interceptor.

Do not purchase a grease trap/interceptor without obtaining a building plan approval including an Industrial Waste approval letter specifying the size and design of the interceptor that will be required. Purchasing an interceptor prior to Industrial Waste approval exposes the purchaser to risk of rejection and replacement costs.

Additionally, grease traps/interceptors less than 100 gallons (minimum liquid holding capacity) will not be approved for installation.

1. Step One

To determine the appropriate grease trap size, calculate the total number of fixture units which will be connected to the trap. The following fixture unit counts shall be assigned to each different kind of fixture:

Indirectly Connected Plumbing Fixtures

Using a floor sink or hub drain.

Fixture Type

Trap and Trap Arm Size 

Fixture Units

3-compartment sink

2", 3”, 4”

4, 6, 8

2-compartment sink

2”, 3”, 4”

4, 6, 8

1-compartment sink

2", 3”, 4”

4, 6, 8

Dishwasher

3”, 4”

6, 8

Garbage disposal/grinder

Prohibited

N/A

Wok stove

2", 3”, 4”

4, 6, 8

Hand sink

2", 3”, 4”

2, 3, 4

Mop sink

2", 3", 4"

2, 3, 4

Floor sink receiving cold, clear water
(eg. condensate water, beverage station, etc.)
2", 3", 4" 2, 3, 4

Hub drain receiving cold, clear water
(eg. condensate water, beverage station, etc.)

2", 3", 4" 0

Directly Connected Plumbing Fixtures

Fixture Type

Trap and Trap Arm Size 

Fixture Units

Hand sink

2", 3"

0, 0

Mop sink

2", 3", 4"

2, 3, 4

Floor drains

2", 3", 4"

2, 3, 4

Floor sinks
(no food service equipment directly above)

3", 4"

3, 4

Trench drains
(receiving condensate from ice bins, coolers, beverage only, etc.)
2", 3", 4" 2, 3, 4
Trench drains
(receiving grease-bearing wastes and solids)
2", 3", 4" 4, 6, 8

2. Step Two

Determine the minimum flow rating of the grease trap by multiplying the total fixture unit count times three gallons/minute:

Grease trap flow rating = Total fixture unit count x 3 gallons/minute
 

3. Step Three

Calculate the minimum liquid holding capacity of the trap by multiplying the grease trap flow rating (in gallons per minutes) times twelve minutes:

Grease trap liquid holding capacity (gallons) = grease trap flow rating x 12 minutes

Industrial Waste staff shall apply this grease trap sizing criteria in combination with best professional judgment as a part of the approval process. In many cases, a larger grease trap may be required than the one specified by the sizing criteria to adequately protect the City’s sanitary sewer and wastewater treatment plants. In rare circumstances, a smaller grease trap may be approved.

Grease traps/interceptors less than 100 gallons (minimum liquid holding capacity) will not be approved for installation.

Commercial Food Preparation facilities which utilize a dishwasher must install a minimum 500-gallon (liquid holding capacity) grease interceptor. This provides the 7-minutes retention time required in grease interceptor compartment 1, and 5-minutes retention time in grease interceptor compartment 2, equaling the 12-minutes total. This also helps retain high temperatures within the grease interceptor until cooling and separation of spent FOG (Fats, Oil and Grease) can occur, along with solids settling to prevent discharging these materials into the sanitary sewer.

Clear Water / Non-Grease-Bearing Waste Fixtures:
  • Hand sinks are not required to be plumbed to the grease trap.
  • Fixtures receiving non-grease-bearing wastes may be drained through a grease trap, but shall not be included for grease trap sizing unless routed to a floor sink (i.e., condensate from coolers, beverage only, etc.).
  • Floor sinks with condensate/beverage are not counted as floor sinks if they have a 1" lip.

Grease-Bearing Waste Fixtures:

  • For indirect waste systems where floor sinks and hub drains are used as receptors for dishwashers, 1-, 2- and 3-compartment sinks, etc., the fixture unit count shall be twice (2x) the floor sink or hub drain fixture unit count.
  • Facilities using dishwashers or wok stoves are required to install 2-compartment grease traps or interceptors with a 12-minute total retention time.
  • In most cases, grease trap sizing will include a 12-minute total retention time.  This is necessary to adequately protect the City’s sanitary sewer and wastewater treatment plants from grease or solids.
  • In many cases, a larger grease trap may be required than the one specified by the sizing criteria. This is left to the discretion of Industrial Waste personnel.

Garbage Disposals/Grinders & Food Waste Collection Systems:

  • As of January 2008, garbage disposals/grinders are prohibited in commercial kitchens and other industrial users of the sanitary sewer system. For additional information, refer to this 2011 Food Waste Disposal Memorandum.
  • Food waste collection systems that require a potable make-up water supply shall:
    • Not exceed a flow rate of 1.28 gallons per minute for the make-up supply; and
    • Not include a pre-rinse spray valve.
  • Food waste collection systems that do not require a potable make-up water supply, such as straining baskets, may include a pre-rinse spray valve provided it complies with the Uniform Plumbing Code (UPC) and local amendments to the UPC code.
  • To receive approval to add a food waste collection system or food digestor, complete the Preliminary Request for Food Digestor Installation Form  and submit it to Austin Water Industrial Waste for plan review via mail or email:
      
    MailIndustrial Waste – Austin Water
    6310 Wilhelmina Delco Dr., 3rd Floor
    Austin, TX 78752

    EmailIndustrialWaste@austintexas.gov

Grease Interceptor Installation Variance Request:

  • The Grease Interceptor Installation Variance Request (GIIVR) form is used to request to operate without a grease interceptor from the Industrial Waste program. This applies to only certain facilities including those serving pre-packaged foods in the original unopened container, providing drinks only or cutting fruit as some examples.

    If you feel this is applicable to your project, please fill out the GIIVR form and submit it along with the other required Plan Review documents. Industrial Waste staff will determine whether a grease interceptor is required upon initial submittal.
     

  • After a grease interceptor waiver from Industrial Waste has been approved:
    • If the approved facility subsequently causes a Sanitary Sewer Overflow or issues within the wastewater collection system, they will be required to install a grease interceptor.
    • If the food type or food service changes, Industrial Waste staff will reassess whether a grease interceptor is needed based on the change in operations.

Disclaimer: Building Plans vary greatly from one project to another. Please keep in mind that the information above is applicable to most, but not all projects. Additionally, the information above is not intended to, and may not cover every situation, especially for unique or highly complicated projects. 

For more information, visit the Industrial Waste Plan Review (Pretreatment Plan Review) webpage or contact the IW staff with questions by email at IndustrialWaste@austintexas.gov or by phone at 512-974-7293.